Errors Occurring On Screen Data Initialization And Transmission - Omron NT631 Series Reference Manual

Programmable terminals
Hide thumbs Also See for NT631 Series:
Table of Contents

Advertisement

Responding to Displayed Error Messages
Error
Other tool is accessing.
Remove trouble execution
fails. (when clearing an error
from error log screen)
Connection failed.
(when starting the Device
Monitor function)
Set Comm. Method to NT
Link (1:1 or 1:N)
(when the Device Monitor
menu is being displayed)

6-2-3 Errors Occurring on Screen Data Initialization and Transmission

Message
[Flash Memory Error]
Flash Memory I/O Error.
If this happens frequently, Flash
Memory may be broken.
Press Reset Switch to restart.
[Calendar Data Error]
Calendar Data is incorrect.
Set to the MAINTENANCE
MODE and set Calendar Data.
[Tool Transmit Error]
∗∗∗∗ Error detected while
downloading by the following
case:
case:
S faulty connecting cable.
S corrupted data by noise.
[Tool Transmit Error]
Check Sum Error occurs while
downloading by the following
case:
S corrupted data by noise.
[Tool Transmit Error]
Time-out Error occurs while
downloading by the following
case:
S faulty connecting cable.
[Tool Transmit Error]
Reception was failed by Buffer
Over Flow Error.
Downloaded from
Elcodis.com
electronic components distributor
Probable cause
A Programming Device
connected to the PC is
performing an operation such
as online editing.
(when attempting to change
the operating mode or clear
forced status)
The cause of the PC error
has not been eliminated.
The Device Monitor function
was called when the PT was
not connected to a PC that
supports Device Monitor.
The communications protocol
set at the PT is not 1:1 NT
Link or 1:N NT Link.
The table below shows the errors that can occur when the PT data is initialized,
and during data setting and transmission, and their remedies.
Cause
There is a hardware fault, or the
flash memory (memory for
storing screen data) has reached
the end of its service life.
Hardware fault, or system
program error
The connecting cable is
defective.
Malfunction due to external noise
Malfunction due to external noise
The connecting cable is
defective.
The receive buffer has
overflowed.
Remedy
Try the operation again after disconnecting the
Programming Device.
Eliminate the cause of the error that you are trying to
clear. For details, refer to the PC's Operating Manual.
Check the model of the PC that is connected. (Refer to
2-17-1 Compatible Systems for a table of PCs that
support the Device Monitor function.)
Check the memory switches (fourth screen) and set the
connected PC's serial port protocol to 1:1 NT Link or
1:N NT Link. Set the same protocol in the PC.
Remedy
If the same message is displayed even after
clearing the screen data or transmitting screen
data several times, contact your OMRON
service center.
Set the calendar clock again from the System
Menu. If the problem recurs, delete the program
in the System Installer mode, then re-install the
program. (Refer to Section 6 of the Setup
Manual .)
If this does not solve the problem, contact your
OMRON service center.
Check the cable connection and perform a
conductivity test. If there is a fault, replace the
cable. (Refer to the appendix Making the Cable
for Connecting a PC in the Setup Manual .)
Carry out grounding work in accordance with the
conditions. (Refer to Grounding in section 3 in
the Setup Manual .)
Carry out grounding work in accordance with the
conditions. (Refer to Grounding in section 3 in
the Setup Manual .)
Check the cable connection and perform a
conductivity test. If there is a fault, replace the
cable.
Retransmit the data from the Support Tool.
Section
6-2
417

Advertisement

Table of Contents
loading

This manual is also suitable for:

Nt31 seriesNt21 seriesNt31c seriesNt631c series

Table of Contents