Ambient Conditions

Ambient conditions In operation
Max. ambient tem‐
+5 ℃ to +45 ℃
perature
Max. temperature
Temporal temperature changes
gradient
up to 3 K per minute
Humidity
Min. rel. humidity: 5 %
Max. rel. humidity: 85 %
Min. abs. humidity: 1 g/m
Max. abs. humidity: 25 g/m
Non-condensing
according to climatic class 3K3
acc. to EN 60721-3-3
Air pressure
Up to 3,000 m above sea level
acc. to EN 61131-2
Mechanical
Max. vibration:
strength
Frequency range: 10 to 150 Hz
Excursion: 0.075 mm for 10 to 57
Hz
Acceleration: 1 g for 57 to 150 Hz
acc. to EN 60068-2-6
Degree of pollution 2
Overvoltage cate‐
2
gory
4.7

Standards

4.7.1

Used Standards

Utilization category according to EN IEC
60947-5-2
AC-12, AC-15, DC-12, DC-13
Difference time of the outpus (LB at first)
Connection type of the switching contacts Screw terminal, 2 × 2-pin
Fig.4-9:
Parameters for LA and LB outputs
The manufacturer and operator of the higher-level overall system,
e.g. of a machinery, is responsible for complying with the national
and international safety and accident prevention regulations which
apply to the specific use.
Transport
-20 ℃ to +60 ℃
Temporal temperature changes up
to 3 K per minute
Min. rel. humidity: 5 %
Max. rel. humidity: 75 %
3
Min. abs. humidity: 1 g/m
Max. abs. humidity: 25 g/m
3
Non-condensing
according to climatic class 2K2 acc.
to EN 60721-3-2
Up to 3,000 m above sea level acc.
to EN 61131-2
Max. shock:
15 g 11 ms
acc. to EN 60068-2-27
No disturbance of the function
2
-
Fig.4-10:
Ambient Conditions
The system components of the VAM 12.1/VAM 42.1 correspond to the following
standards:
Bosch Rexroth AG
Technical Data
50 mA / 24 V
Typ. 200 ms
Storage
-20 ℃ to +60 ℃
Temporal temperature changes
up to 3 K per minute
Min. rel. humidity: 5 %
Max. rel. humidity: 85 %
3
Min. abs. humidity: 1 g/m
Max. abs. humidity: 25 g/m
3
Non-condensing
according to climatic class 1K2
acc. to EN 60721-3-1
Up to 3,000 m above sea level
acc. to EN 61131-2
Max. shock:
15 g 11 ms
acc. to EN 60068-2-27,
No disturbance of the function