Basic Setup Page - Delta DVP02TK-S Manual

Temperature control module
Hide thumbs Also See for DVP02TK-S:
Table of Contents

Advertisement

TK
TU
Attribute
Add.
CR#
(Hex)
R: Able to read data by FROM instruction. W: Able to write data by TO instruction.
Error Code
Bit0
Power Supply abnormal
Bit1
Hardware abnormal
Bit2
CH1 conversion error
Bit3
CH2 conversion error
Bit4
CH1 circuit control abnormal
Bit5
CH2 circuit control abnormal
Bit6
Manually / Auto Output
Bit7-15
Reserved

2.1.4 Basic Setup Page

TK CH1
TK CH2
TU
Page0
Page10
CR#
Add. (Hex)
Add. (Hex)
00B
0EB
#11
Name
Abnormal
Abnormal
Abnormal
Abnormal
Abnormal
Abnormal
Manually Output
Attribute
Name
R/W
O
Sensor type
Ch ap te r 2 Co n tro l Reg is te r
Description
1
Description
K-1: Channel closed
K0: 0 ~ 5V
K1: 0~10V
K2: 0 ~ 20mA
K3: 4 ~ 20mA
K4: 0 ~ 50mV
K5: Pt100
K6: JPt100
K7: Pt1000
K8: J
K9: K
K10: R
K11: S
K12: T
K13: E
K14: N
K15: B
K16: L
K17: U
K18: TXK
K19: C
K20: PL II
Default
2_
0
Normal
Normal
Normal
Normal
Normal
Normal
Auto Output
Default
K0
2 - 5

Hide quick links:

Advertisement

Table of Contents
loading

This manual is also suitable for:

Dvp02tu-s