Rules for permitted topologies
5.2 Topology rules for S120 Booksize
● Ring wiring is not permitted.
● Components must not be double-wired.
● The following applies to the booksize format:
● The following applies to the chassis format: Line Modules (Active Line, Basic Line, Smart
● The default sampling times may be changed.
● A maximum of 16 measuring systems can be connected to a PPU with NX10.3:
● Only one TM54F is permitted for each PPU and for each NX10.3.
58
Figure 5-1
Example: DRIVE-CLiQ line at the X100 terminal (without Safety Integrated)
– In the servo control and vector U/f control operating modes, only one Line Module may
be connected to the Control Unit. In the vector control operating mode, a maximum of
three further Line Modules may be connected in parallel (i.e. a total of four Line
Modules).
– It is permissible that one Line Module and Motor Modules are connected together to
one DRIVE-CLiQ line in the servo control mode.
– One Line Module and Motor Modules must be connected to separate DRIVE-CLiQ
lines in the vector control mode.
– For booksize format, a parallel connection of Infeed Modules or Motor Modules is not
possible.
Line) and Motor Modules must be connected to separate DRIVE-CLiQ lines.
Example 1: PPU with six axes with six motor measuring systems and six direct
measuring systems as well as NX10.3 with two motor measuring systems and two direct
measuring systems.
Example 2: PPU with five axes with five motor measuring systems and five direct
measuring systems as well as NX10.3 with three motor measuring systems and three
direct measuring systems.
Manual, 03/2013, 6FC5397-2DP40-3BA1