Connectable components
7.8 PN/PN coupler
7.8.2

Configuration

Requirements
Please observe the following preconditions when configuring:
● For SINUMERIK 828D, the "PN-PN-Coupler20" name is already permanently defined; as
● The PN/PN coupler has the IP address 192.168.214.20 (permanently set).
● The I/O address area is 16 bytes from 96 ...111 (index m).
● SINUMERIK 828D must be connected to the PROFINET interface X1.
● A coupling between two SINUMERIK 828D systems is not possible as standard.
Configuration
The device name must be defined in the following cases:
● When commissioning for the first time
● When a device is replaced
The PC must be connected using a crossover cable with, e.g. X2 at the PN/PN coupler.
Procedure:
1. Under "Tools" select → "Set PG/PC interface" →"TCP/IP" → "Intel(R) PRO/100 VM".
2. Under "Target system" select → "Edit Ethernet nodes ...".
3. In the dialog window "Edit Ethernet Nodes", press the "Search..." button under "Nodes
4. In the dialog window "Search Network" select the coupler and press "OK".
214
a consequence, the name must be exactly the same in the connected subnet.
that can be accessed online".
Manual, 03/2013, 6FC5397-2DP40-3BA1