Final Steps When Commissioning Online - Siemens Sinamics G120 Function Manual

Safety integrated
Hide thumbs Also See for Sinamics G120:
Table of Contents

Advertisement

Commissioning
5.12 Setting extended functions
5.12.9

Final steps when commissioning online

Activate settings
Requirement
You are online with STARTER or Startdrive online.
Procedure with STARTER
To activate the settings for the safety functions, proceed as follows:
1. Press the "Copy parameters" button, to create a redundant image of your inverter settings.
2. Press the "Activate settings" button.
3. If the password is the factory default, you are prompted to change the password.
If you try to set a password that is not permissible, the old password will not be changed.
4. Confirm the prompt for saving your settings (copy RAM to ROM).
5. Switch off the inverter supply voltage.
6. Wait until all LEDs on the inverter go dark (no voltage condition).
7. Switch on the inverter supply voltage again.
Your settings are now active.
198
Safety Integrated - SINAMICS G110M, G120, G120C, G120D and SIMATIC ET 200pro FC-2
Function Manual, 01/2017, FW V4.7 SP6, A5E34261271B AD