Configuring PROFIsafe via extended functions

Telegram 30 is preset in the inverter as default.
Configuring the PROFIsafe address
Proceed as follows to configure the PROFIsafe address:
1. Press the "Configuration" button.
2. Enter the same PROFIsafe address in hexadecimal format that you defined in the hardware
configuration.
3. Close the screen form.
You have configured the PROFIsafe address.
Parameter
p9610
Configuring telegram 900
Procedure
Proceed as follows to configure PROFIsafe telegram 900:
1. Press the "Safety inputs" button.
2. Enable telegram 900.
Safety Integrated - SINAMICS G110M, G120, G120C, G120D and SIMATIC ET 200pro FC-2
Function Manual, 01/2017, FW V4.7 SP6, A5E34261271B AD
5.9 Configuring safety functions and PROFIsafe using STARTER
Description
PROFIsafe address (Factory setting: 0000 hex)