Operation
6.5 Safe Stop 1 (SS1)
Switching the motor on after an internal event
Procedure
To switch the motor on after an internal event while SS1 is active, proceed as follows:
1. Deselect function SS1.
2. Issue an OFF1 command (ON/OFF1 = 0).
3. Acknowledge the inverter with the "standard" acknowledge signal.
4. Switch on the motor again (ON/OFF1 = 1).
You have acknowledged the internal event and switched on the motor again.