Advertisement

Commissioning
5.12 Setting extended functions
3. Press the "Safe basic functions" button:
Set the following:
– (A) Set the monitoring time to the maximum value (9000 hours). This means that the
– This monitoring is not required when using the extended functions, as the forced
– (B) Setting not required.
– (C) If required, interconnected the status of the STO function, e.g. with a digital output
4. Close the screen form.
You have set the forced checking procedure (test stop) of the extended functions.
148
forced checking procedure monitoring for the basic functions is deactivated.
checking procedure for the extended functions also includes the forced checking
procedure for the basic functions.
of your choice.
Safety Integrated - SINAMICS G110M, G120, G120C, G120D and SIMATIC ET 200pro FC-2
A
Function Manual, 01/2017, FW V4.7 SP6, A5E34261271B AD