6.9 Response to a discrepancy in the signals transferred via PROFIsafe

6.9
Response to a discrepancy in the signals transferred via PROFIsafe
Drive response
Figure 6-49
The inverter does not set the error bit of the safety functions (= internal event).
After the tolerance time has expired, the inverter signals the discrepancy (fault C01770 or
C30770).
Independent of the voltage levels available, the inverter sets the evaluation of the discrepant
fail-safe digital input into the safe state (= zero) until you acknowledge the inverter using a fail-
safe signal or you switch off the power supply voltage and switch it on again.
Inverter signals
Internal event
"Standard" acknowledgment
Fail-safe acknowledgment
292
Behavior of the inverter in the event of a discrepancy in a fail-safe digital input in PROFIsafe
telegram 900
Safety Integrated - SINAMICS G110M, G120, G120C, G120D and SIMATIC ET 200pro FC-2
Parameter
Included in the PROFI‐
safe telegram
r9722.7
p2103
r9720.7
Function Manual, 01/2017, FW V4.7 SP6, A5E34261271B AD