Interconnecting The Signal For Fail-Safe Acknowledgment - Siemens Sinamics G120 Function Manual

Safety integrated
Hide thumbs Also See for Sinamics G120:
Table of Contents

Advertisement

Commissioning
5.12 Setting extended functions
5.12.2.3

Interconnecting the signal for fail-safe acknowledgment

Preconditions
● You are online with STARTER or Startdrive.
● You have selected the extended functions via onboard terminals.
Procedure with STARTER
To assign the fail-safe acknowledgement signal to a fail-safe digital input, proceed as follows:
1. Press the "Safety inputs/outputs" button.
2. Press the "Configuration" button.
3. Select a free safety-related digital input for the fail-safe acknowledgment signal.
If there are no free fail-safe digital inputs available, you have to acknowledge the safety
function faults using a different method.
4. Close the screen forms.
You have interconnected fail-safe acknowledge signal with a fail-safe digital input.
162
Acknowledging using a fail-safe signal (Page 299)
Safety Integrated - SINAMICS G110M, G120, G120C, G120D and SIMATIC ET 200pro FC-2
Function Manual, 01/2017, FW V4.7 SP6, A5E34261271B AD