Roland R1000 Series Manual page 111

Double sheet detector
Hide thumbs Also See for R1000 Series:
Table of Contents

Advertisement

B0046991 / Rev. 1.6
System parameter 7: Switching the password function on / off.
system param.
password:
Fig.. 60: Switching the password on / off
System parameter 8: Setting the output logic (0-sheet, 1-sheet, 2-sheet outputs).
system param.
level 0-1-2:+24V
Fig.. 61: Setting the output logic
Possible choices:
0 V:
+24 V: The outputs 0-sheet, 1-sheet and 2-sheet are inverted, i.e. the respective signals in
System parameter 9: Deactivating / activating the external calibration via fieldbus.
system param.
ext. adjust:
Fig.. 62: Deactivating / activating the external calibration
Here the external calibration, which is possible via PLC with the signals "teach-in" and "zero
adjust", can be deactivated / activated.
System parameter 10: Indication of system version.
System Param. 10
Version:
Fig.. 63: Indication of system version, here 4P with 3 sensors, Version C, Opto coupler
This factory setting must not be changed!
ROLAND ELECTRONIC GmbH · Otto-Maurer-Str. 17 · DE 75210 Keltern · Phone +49 (0)7236-9392-0 · Fax +49 (0)7236-9392-33
Double Sheet Detector R1000 series E20
7
yes
If no password is activated, then all parameters can be accessed
Attention
at any time. We recommend this only during starting-up the
system. For daily operation the password function should be
activated.
8
As shown in the timing diagrams and the wiring diagrams
the timing diagrams and wiring diagrams must be seen inverted.
The output "Enable" is not affected thereby.
Note
9
no
4P3 CO
Manual
Start-up
111

Hide quick links:

Advertisement

Table of Contents
loading

This manual is also suitable for:

E20

Table of Contents