11.5

Relay Interface Module (Optional)

An optional Relay Interface Module (RIM) uses relay contact closures to indicate
the operating status and alarm condition of the Parallel Capacity/Redundant
system. A maximum of two monitoring accessories (RMPs, RIMs, or SCMs) can be
installed. See Table 11−1 for the number of accessories permitted. Figure 11−2
shows the RIM with its four 15-pin connectors labeled J1 through J4.
The RIM can provide these signals:
UPS AVAILABLE
UPS OFF LINE
UTILITY FAILURE
BATTERY WEAK
11−4
Figure 11−2. Relay Interface Module
(pins 1 and 12) Contacts are closed when the UPS is
offline.
(pins 3 and 13) Contacts are closed when the UPS is
operating in Normal mode.
(pins 6 and 15) Contacts are closed when Utility Failure is
detected.
(pins 5 and 14) Contacts are closed when approximately
2 minutes of battery time is remaining, before the critical
load is lost.
EATON Powerware 9315 Parallel Capacity/Redundant System
164201150
Rev. E www.powerware.com