Installing A Remote Monitor Panel (Optional); Installation Procedures - Eaton Powerware 9315 Installation And Operation Manual

Parallel capacity/redundant system
Hide thumbs Also See for Powerware 9315:
Table of Contents

Advertisement

Installing a Remote
Monitor Panel (Optional)
4.1

Installation Procedures

As an option, you can install Remote Monitor Panels (RMPs) to monitor the
operation of the Parallel Capacity/Redundant system from virtually any location
within your facility, up to 500 feet from the System Bypass Module (SBM). You can
flush-mount or surface-mount an RMP on a desktop or on a wall, wherever you
have a serial interface line. A maximum of two monitoring accessories (RMPs,
RIMs, or SCMs) can be installed. See Table 4−1 for the number of accessories
permitted. Figure 4−1 shows an RMP . Drawing 164201150−17 in Appendix A
shows the enclosure dimensions and knockout patterns.
Remote Monitor Panel
2
1
1
EATON Powerware 9315 Parallel Capacity/Redundant System
164201150
Rev. E www.powerware.com
Table 4−1. Optional Monitoring Accessories
Number and Type of Accessories Permitted
Relay Interface Module
Supervisory Contact Module
2
1
1
44
2
1
1
4−1