To Install A Rim; Figure 5−2. Terminal Block Bracket - Eaton Powerware 9315 Installation And Operation Manual

Parallel capacity/redundant system
Hide thumbs Also See for Powerware 9315:
Table of Contents

Advertisement

5.2

To install a RIM:

1.
Securely mount the RIM.
2.
Install wiring from the RIM using ½-in. conduit through the cable entry panels
in the top of the SBM control section (refer to the enclosed switchboard vendor
drawings for the location of the conduit landing plate).
3.
If not already installed, locate the RMP adapter cable assembly (Figure 5−2) in
the spare parts kit. Mate the DB−9 connector on the back of the terminal
block to the DB−9 connector (Port 1) on the Customer Interface Panel of the
SBM (refer to Drawing 164201150−13 in Appendix A). Use two screws from
the spare parts kit to secure the terminal block bracket to the Customer
Interface Panel.
Connect to
Port 1 (DB−9) on
Customer Interface Panel
5−2
Figure 5−2. Terminal Block Bracket
EATON Powerware 9315 Parallel Capacity/Redundant System
FUSE
TERMINAL
BLOCK
(TB3)
164201150
Rev. E www.powerware.com