7.3
Optional Modes of Parallel Operation:
Maintenance Bypass and Redundant CBP
There are two optional modes of operation in this Parallel Capacity/Redundant
system:
In Maintenance Bypass mode (optional), the SMB bypass supplies the load and
isolates the SSBM and UPMs for maintenance purposes.
In Redundant CBP mode (optional), if the CBP breaker fails to close during a
manual or automatic operation, the SSBM automatically closes the MBP
breaker to maintain power to the critical load.
7−6
EATON Powerware 9315 Parallel Capacity/Redundant System
164201150
Rev. E www.powerware.com