NOTE: Before installing an RMP , be sure you have prepared the SBM according to
the instructions in Chapter 2.
4.2

To install an RMP:

1.
Securely mount the RMP(s).
2.
Install wiring from the RMP using ½-in. conduit through the cable entry panels
in the top of the SBM control section (refer to the enclosed switchboard vendor
drawings for the location of the conduit landing plate).
3.
In the spare parts kit, locate the RMP adapter cable assembly (Figure 4−2).
Mate the DB−9 connector on the back of the terminal block to the DB−9
connector (Port 1) on the Customer Interface Panel of the SBM (refer to
Drawing 164201150−13 in Appendix A). Use two screws from the spare parts
kit to secure the terminal block bracket to the Customer Interface Panel.
Connect to
Port 1 (DB−9) on
Customer Interface Panel
EATON Powerware 9315 Parallel Capacity/Redundant System
164201150
Rev. E www.powerware.com
Figure 4−2. Terminal Block Bracket
FUSE
TERMINAL
BLOCK
(TB3)
4−3