Configure Response Time; Configure Alert Handling - Emerson Micro Motion 2700 Configuration And Use Manual

Transmitters with intrinsically safe outputs
Hide thumbs Also See for Micro Motion 2700:
Table of Contents

Advertisement

Configure device options and preferences
5.4.2

Configure Response Time

Display
ProLink III
Field Communicator Not available
Overview
Response Time is used to apply a different algorithm to the calculation of process variables
from the raw process data.
Restriction
Response Time is available only on systems with the enhanced core processor.
Procedure
Set Response Time as desired.
Option
Normal (Legacy)
Special (Legacy)
Normal - Optimal Filtering
Low Filtering - Fastest Re-
sponse
High Filtering - Smoothest
Output
Service
5.5

Configure alert handling

The alert handling parameters control the transmitter's response to process and device
conditions.
78
Not available
Device Tools > Configuration > Process Measurement > Response > Response Time
Description
Transmitter calculates process variables at the standard speed. This op-
tion is selected if this parameter was configured on an earlier version of
ProLink III software.
Transmitter calculates process variables at a faster speed. This option is
selected if this parameter was configured on an earlier version of ProLink
III software.
Transmitter calculates process variables at standard filtering and speed.
Transmitter calculates process variables at the fastest speed.
Transmitter calculates process variables at the smoothest (least noisy)
response to changes in the process.
For factory use only.
Micro Motion Model 2700 Transmitters with Intrinsically Safe Outputs

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents