Configure AO Cutoff

Display
ProLink III
Field Communicator
AO Cutoff (Analog Output Cutoff) specifies the lowest mass flow rate, volume flow rate, or
gas standard volume flow rate that will be reported through the mA Output. Any flow rates
below AO Cutoff will be reported as 0.
Restriction
AO Cutoff is applied only if mA Output Process Variable is set to Mass Flow Rate, Volume Flow Rate, or
Gas Standard Volume Flow Rate. If mA Output Process Variable is set to a different process variable, AO
Cutoff is not configurable, and the transmitter does not implement the AO cutoff function.
Procedure
Set AO Cutoff as desired.
The default values for AO Cutoff are as follows:
Primary mA Output: 0.0 g/sec
Secondary mA Output: Not-A-Number
Tip
For most applications, the default value of AO Cutoff should be used. Contact customer service
before changing AO Cutoff.
Interaction between AO Cutoff and process variable cutoffs
When mA Output Process Variable is set to a flow variable (for example, mass flow rate or
volume flow rate), AO Cutoff interacts with Mass Flow Cutoff or Volume Flow Cutoff. The
transmitter puts the cutoff into effect at the highest flow rate at which a cutoff is
applicable.
Configuration and Use Manual
Default values for Lower Range Value (LRV) and Upper Range Value (URV)
LRV
0%
0
0
Not available
Device Tools > Configuration > I/O > Outputs > mA Output
Configure > Manual Setup > Inputs/Outputs > mA Output 1 > mA Output Settings >
MAO Cutoff
Configure > Manual Setup > Inputs/Outputs > mA Output 2 > mA Output Settings >
MAO Cutoff
Integrate the meter with the control system
URV
100%
10
10
93