Integrate the meter with the control system
Note
The service port responds automatically to a wide range of connection requests. It is not
configurable.
6.6.1
Configure HART/Bell 202 communications
HART/Bell 202 communications parameters support HART communications with the
transmitter's primary mA terminals over a HART/Bell 202 network.
Configure basic HART parameters
Basic HART parameters include the HART address, HART tags, and the operation of the
primary mA Output.
HART/Bell 202 communications parameters support HART communication with the
transmitter's primary mA terminals over a HART/Bell 202 network. The HART/Bell 202
communications parameters include:
•
•
•
•
Procedure
1.
2.
110
HART Address (Polling Address)
mA Output Action
Burst Parameters (optional)
HART Variables (optional)
Set HART Address to a value that is unique on your network.
•
Default: 0
•
Range: 0 to 15
Tips
•
The default address is typically used unless you are in a multidrop environment.
•
Devices using HART protocol to communicate with the transmitter may use either HART
Address or HART Tag (Software Tag) to identify the transmitter. Configure either or both,
as required by your other HART devices.
Ensure that mA Output Action is configured appropriately.
Option
Description
Enabled (Live)
The primary mA Output reports process data as configured.
Disabled (Fixed)
The primary mA Output is fixed at 4 mA and does not report process
data.
Micro Motion Model 2700 Transmitters with Intrinsically Safe Outputs