6.5.1

Configure a basic event

Display
ProLink III
Field Communicator Not available
Overview
A basic event is used to provide notification of process changes. A basic event occurs (is
ON) if the real-time value of a user-specified process variable moves above (HI) or below
(LO) a user-defined setpoint. You can define up to two basic events. Event status can be
queried via digital communications, and a Discrete Output can be configured to report
event status.
Procedure
1.
2.
3.
4.
5.
6.5.2

Configure an enhanced event

Display
ProLink III
Field Communicator Configure > Alert Setup > Discrete Events
Configuration and Use Manual
Enhanced event model
Not available
Device Tools > Configuration > Events > Basic Events
Select the event that you want to configure.
Specify Event Type.
Option
Description
HI
x > A
The event occurs when the value of the assigned process variable (x) is
greater than the setpoint (Setpoint A), endpoint not included.
LO
x < A
The event occurs when the value of the assigned process variable (x) is
less than the setpoint (Setpoint A), endpoint not included.
Assign a process variable to the event.
Set a value for Setpoint A.
(Optional) Configure a Discrete Output to switch states in response to the event
status.
Not available
Device Tools > Configuration > Events > Enhanced Events
Integrate the meter with the control system