1.6.6 NFC-50/100
The NFC-50/100 is a single channel, 50 watt, 25 V
notification applications, or both. Automatic activation of the NFC-50/100 is possible via eight Command Input Circuits (CMD) or via
the ANN BUS serial communications link from the NFW-100X FACP.
1.6.7 NFC-FFT
An NFC-FFT Fire Fighter Telephone provides supervision, annunciation, and control for local and remote telephone handsets. The NFC-
FFT's keypad provides indications of phone activation and corresponding trouble conditions. .
1.6.8 FWSG Wireless Gateway
The FWSG Wireless Gateway acts as a bridge between a group of wireless fire devices and a FlashScan SLC loop on the NFW-100X. It
is powered by the SLC loop or by a regulated, external 24VDC UL-listed power supply evaluated for life safety. Available wireless
devices include a photo detector, a Acclimate detector, a fixed-temperature heat detector, a rate-of-rise heat detector, a monitor module,
and a relay module. A maximum of 100 wireless devices can be used in the system. For details about wireless devices, system setup, and
operation, see the SWIFT
NOTE: The FWSG, as part of the wireless network, has been tested for compliance with the Federal Communications Commission (FCC)
requirements of the United States Government. It has not been evaluated for use outside the USA. Use of this system outside the USA is
subject to local laws and rules to which this product may not conform. It is the sole responsibility of the user to determine if this product may
be legally used outside the USA.
1.6.9 ANN-BUS Annunciators/Modules
WARNING: RISK OF ELECTRICAL SHOCK AND EQUIPMENT DAMAGE
!
DISCONNECT ALL SOURCES OF POWER (AC AND DC) BEFORE INSTALLING OR REMOVING ANY MODULES OR
WIRING.

Guidelines

A variety of optional annunciation devices can be connected to an ANN-BUS communication circuit. ANN Series devices can be
connected to the primary communication circuit (EIA-485) terminals on TB9. A secondary communication circuit for these devices
is available at TB8. Each ANN-BUS communication circuit supports up to eight (8) annunciators. Compatible devices include the
following:
– N-ANN-80 LCD Annunciator (UL applications only)
– N-ANN-100 LCD Annunciator (FM applications only)
– N-ANN-S/PG Serial/Parallel Printer Interface Module

– N-ANN-I/O LED Driver Module

– N-ANN-LED Annunciator Module (alarm, trouble, supervisory LEDs)
– N-ANN-RLED Annunciator Module (red alarm LEDs only)
– N-ANN-RLY Relay Module (can be mounted in the supplied FACP chassis)
When operating two ANN-BUS circuits, only one N-ANN-S/PG Printer module can be used in the system.
The panel is capable of operating a primary ANN-BUS (TB9) and a secondary ANN-BUS (TB10) simultaneously.
Only one audio system (NFC-50/100 or NFV-25/50) may be connected to the ANN-BUS.
N-
N-
ANN-80/
ANN-100 Remote Fire Annunciators
The N-ANN-80 and N-ANN-100 Annunciators are 80 character, backlit LCD remote fire annunciators. They mimic the display on the
control panel and will annunciate device type, point alarm, trouble or supervisory conditions, zone assignments plus any custom alpha
labels programmed into the FACP. The annunciators also provide system status LEDs to display AC Power, Alarm, Trouble, Supervisory
and Alarm Silenced conditions. Additionally, the annunciators are capable of remotely performing critical system functions such as
Acknowledge, Silence, Reset and Drill. Communication between the annunciators and the FACP is accomplished over a two wire RS-
485 serial interface employing the ANN-BUS communication format. The devices are powered, via two additional wires, from either the
host FACP or remote UL-listed, filtered, regulated, power supply.
The function buttons and piezo sounder may be individually enabled and disabled through the FACP software. Refer to "ANN-80/100
Options" on page 98 for a description of this feature and programming information.
N-
ANN-S/PG Serial/Parallel Interface Module
The N-ANN-S/PG Serial/Parallel Interface module allows the connection of a remote serial or parallel printer to the FACP for a real-
time log of system events, detector status reports and event history. The module is provided with a plastic enclosure for surface mount-
ing.
N-
ANN-I/O LED Driver Module
The N-ANN-I/O is an LED driver module that can be used in a wide variety of applications, including as an interface with most custom-
ized graphic annunciators. The N-ANN-I/O can drive up to 40 LEDs. The module is provided with a plastic wall mount.
NFW-100X Manual — P/N LS10131-001NF-E:C 7/25/2018
RMS
®
Smart Wireless Integrated Fire Technology Instruction Manual #LS10036-000NF-E.
, emergency voice evacuation panel that may be used for fire applications, mass
Product Description
19