3
SPECIFICATIONS
3.4.22
The number of conversion periods to check a change in measured temperature values is
set for each channel. (Refer to Section 3.2.4)
(1) Setting methods
(2) Default value
3.4.23
A scaling range of measured temperature values is set for each channel in units of
0.1
(1) Setting methods
(2) Default value
3
- 54
3.4 Buffer Memory
3.4.22 CH[ ] Rate alarm warning detection period (Un\G126 to Un\G133)
CH[ ] Rate alarm warning detection period (Un\G126 to Un\G133)
(a) For use of the rate alarm, change the setting value.
(b) Set the number of conversion periods in buffer memory.
• Settable range: 1 to 6000(times)
(c) Turn on Operating condition setting request (Y9) to activate the setting.
All channels are set to "0".
POINT
(1) When a value out of the above setting range is set, an error (error code: 70 )
occurs on the corresponding channel. Then, the following occurs.
• Error code (71 ) is stored into the Error code (Un\G19). (Refer to Section
8.1).
• Error flag (XF) turns on.
• The module operates with setting before the error occurence.
(2) Set "Enable" in Warning output enable/disable (Un\G46). When "Disable" is
set, the settings of CH
Un\G133) is ignored.
CH[ ] Rate alarm upper/lower limit values (Un\G134 to Un\G149)
.(Refer to Section 3.2.4)
(a) For use of the rate alarm, change the setting value.
(b) Set the range in buffer memory.
• Settable range:-32768 to 32767
(c) Turn on Operating condition setting request (Y9) to activate the setting.
All channels are set to "0".
Rate alarm warning detection period (Un\G126 to