3
SPECIFICATIONS
3.4.20
A width for scaling conversion is set.
(1) Setting methods
(2) Default value
3
- 52
3.4 Buffer Memory

3.4.20 CH[ ] Scaling width upper/lower limit values (Un\G78 to Un\G93)

CH[ ] Scaling width upper/lower limit values (Un\G78 to Un\G93)
(a) For use of the scaling function, change the setting value.
(b) Set the scaling range value in buffer memory.
• Settable scaling range: -32768 to 32767
(c) Turn on Operating condition setting request (Y9) to activate the setting.
All channels are set to "0".
POINT
(1) When "Invalid" ("0") is set in Scaling valid/invalid setting (Un\G58), the setting
of CH
Scaling width upper/lower limit values (Un\G78 to Un\G93) is ignored.
(2) If the same value is set for the upper limit and the lower limit, an error (error
code: 91 ) occurs on the corresponding channel. Then, the following occurs.
• Error code (91 ) is stored into Error code (Un\G19). (Refer to Section
8.1).
• Error flag (XF) turns on.
• The module operates with setting before the error occurence.