3
SPECIFICATIONS
3.4.5
"Thermal electromotive force values" input from thermocouples are converted into
"temperature values" to check values of detected temperature.
(1) Data storage
[Setting example 1]
Figure 3.23 Storage example 1 of CH
Figure 3.24 Storage example 2 of CH
3
- 38
3.4 Buffer Memory

3.4.5 CH[ ] Measured temperature value (Un\G11 to Un\G18)

CH[ ] Measured temperature value (Un\G11 to Un\G18)
The measured temperature value rounded off to one decimal place is multiplied by 10
and the result is stored into buffer memory in 16-bit signed binary. (Drop the second
decimal place and later.)
When the measured temperature value is 123.025
b15 b14 b13 b12 b11 b10
0
0
0
0
0
When the measured temperature value is -123.0
b15 b14 b13
b12 b11 b10
1
1
1
1
1
POINT
(1) When disconnection is detected or checked with a monitor, the values set in
Conversion setting for disconnection detection (Un\G164, Un\G165) or
Disconnection state conversion setting (Un\G164, Un\G165) are stored into
the CH
Measured temperature value (Un\G11 to Un\G18). (Refer to Section
3.4.25, Section 3.4.26)
(2) After the disconnection recovery, normal measured temperature value is
automatically stored.
b9
b8
b7
b6
1
0
0
1
1
Measured temperature value (Un\G11 to Un\G18)
b9
b8
b7
b6
0
1
1
0
0
Measured temperature value (Un\G11 to Un\G18)
1230 is stored.
b5
b4
b3
b2
b1
0
0
1
1
1
-1230 is stored.
b5
b4
b3
b2
b1
1
1
0
0
1
b0
0
b0
0