Conversion enable/disable setting (Un\G0)

Temperature conversion enable/disable status is set for each channel.
(1) Setting methods
(a) Set enable/disable status for each channel in buffer memory.
[Setting example] Setting enable status for channel 1 and 2
(b) Turn on Operating condition setting request (Y9) to activate the setting.
(2) Default value
The default value is set to "Disable" (00FF
POINT
b15 b14 b13 b12 b11 b10
0
0
0
0
0
Data for b8 to b15 are fixed to "0"
Figure 3.20 Setting of enable/disable status (Un\G0)
b15 b14 b13 b12 b11 b10
0
0
0
0
0
Figure 3.21 Setting example of enable/disable status (Un\G0)
Setting "Disable" (1) for unused channels can prevent unnecessary disconnection
detection or monitoring disconnection state.
3.4.2 Conversion enable/disable setting (Un\G0)
b9
b8
b7
b6
b5
0
0
0
CH8 CH7 CH6 CH5 CH4 CH3 CH2 CH1
b9
b8
b7
b6
b5
0
0
0
1
1
1
) for all channels.
H
3.4 Buffer Memory
b4
b3
b2
b1
b0
0: Conversion enabled
1: Conversion disabled
b4
b3
b2
b1
b0
1
1
1
0
0
3
- 35
1
2
3
4
5
6
7