3
SPECIFICATIONS
3.4.24
Mode switching setting (Un\G158, Un\G159)
This area is used to switch the mode between normal mode and offset/gain setting mode.
This mode can be switched without resetting the programmable controller CPU.
Setting methods
(a) Set the setting value of the switching target mode.
(b) To switch the mode, turning on Operating condition setting request (Y9) after
(c) When the mode is switched completely, this area for Un\G158 and Un\G159 is
POINT
Table 3.17 Switching target mode and setting value
Switching target mode
Normal mode
Offset/gain setting value mode
setting the value is required.
cleared to "0".
If a value other than the setting values in Table 3.17 is written, mode switching is
not performed.
3.4.24 Mode switching setting (Un\G158, Un\G159)
Setting value
Un\G158
Un\G159
0964
H
4144
H
3.4 Buffer Memory
1
2
4144
H
3
0964
H
4
5
6
7
8
3
- 55