Wiring; Wiring Precautions - Mitsubishi Melsec-Q Series User Manual

Channel isolated thermocouple input module. gx configurator-ti
Hide thumbs Also See for Melsec-Q Series:
Table of Contents

Advertisement

4
SETUP AND PROCEDURES BEFORE OPERATION
4.4

Wiring

The following explains the wiring precautions and module connection example.
4.4.1

Wiring precautions

External wiring that is less susceptible to noise is required as a condition of enabling a
highly reliable system and making full use of the capabilities of the Q68TD-G-H02(H01).
(1) Use separate cables for the AC control circuit and the external input
signals of the Q68TD-G-H02(H01) to avoid the influence of the AC side
surges and inductions.
(2) Always place the thermocouple at least 100mm away from the main
circuit cables and AC control circuit lines. Fully keep it away from high-
voltage cables and circuits, which include high frequency waves, such
as an inverter's load circuit. Not doing so will cause the module more
susceptible to noises, surges and inductions.
(3) The following wiring is required for the product to comply with the EMC
and Low Voltage Directives.
Q68TD-G-H02(H01)
Figure 4.4 Wiring complying with EMC and LOW Voltage Directives
(a) Use shielded cables for every external wiring and use the AD75CK cable clamp to
(b) For wiring between A6CON4 and a relay terminal block, use shielded cables to
(c) Before touching the relay terminal block, always touch the grounded metal to
A6CON4
ground to the panel. AD75CK can ground four cables together when using cables
with outer diameter of about
ground to the panel. In addition, keep the wiring distance within 3m.
discharge the electricity charged in the body.
In a control panel
Relay
terminal
block
20(7.87) to 30cm
(11.81 inch)
7mm.
4.4 Wiring
4.4.1 Wiring precautions
1
2
3
4
5
AD75CK
Strip off
the outer
6
sheath
7
8
4
- 6