3
SPECIFICATIONS
3.4.18
This area is for checking the scaling function valid/invalid status for each channel.
(1) Setting methods
(2) Default value
[Program example]
3
- 50
3.4 Buffer Memory

3.4.18 Scaling valid/invalid setting (Un\G58)

Scaling valid/invalid setting (Un\G58)
(a) Scaling valid/invalid setting is set for each channel.
b15 b14 b13 b12 b11 b10
0
0
0
0
Data for b8 to b15 is fixed to "0".
Figure 3.36 Setting of Scaling valid/invalid setting (Un\G58)
(b) Turn on Operating condition setting request (Y9) to activate the setting.
All channels are set to "Invalid" (00FF
Program example with a condition of the following is below.
• Scaling range: -100 to 500
• Scaling width: 0 to 100.0% (lower limit value = 0, upper limit value = 100)
Figure 3.37 Program example of scaling function
b9
b8
b7
0
0
0
0
CH8 CH7 CH6 CH5 CH4 CH3 CH2 CH1
).
H
(lower limit value = -1000, upper limit value = 5000)
b6
b5
b4
b3
b2
Sets CH1 scaling function to
"enable"
Sets CH1 scaling range lower
limit value
Sets CH1 scaling range upper
limit value
Sets CH1 scaling width lower
limit value
Sets CH1 scaling width upper
limit value
Turns ON operating condition
seting request (Y9)
Turns OFF operating condition
setting request (Y9)
b1
b0
0: Valid
1: Invalid