3
SPECIFICATIONS
3.2

Function List

The following table lists the Q68TD-G-H02 (H01) functions.
Item
Temperature conversion
This function allows temperature data to be imported by connecting a thermocouple.
function
Temperature data are 16-bit signed binary (-2700 to 18200) and stored into buffer memory.
(1) Sampling processing
(2) Averaging processing
Temperature conversion
system
(3) Primary delay filter
Conversion enable/disable
This function specifies whether temperature conversion is enabled or disabled on each
function
channel.
Thermocouple type
This function sets the type of thermocouple on each channel.
selection function
Disconnection detection
This function checks the disconnection of the connected thermocouple on each conversion-
function
enabled channel.
(Q68TD-G-H02 only)
Conversion setting for
This function is to select a value to be stored in the CH
disconnection detection
(Un\G11 to Un\G18) from "Up scale", "Down scale" or "Given scale" when disconnection is
function
detected.
(Q68TD-G-H02 only)
Disconnection monitor
This function checks the disconnection of the connected thermocouple on each conversion-
function
enabled channel.
(Q68TD-G-H01 only)
Disconnection state
This function is to select a value to be stored in the CH
conversion setting function
(Un\G11 to Un\G18) from "Up scale", "Down scale" or "Given scale" when disconnection is
(Q68TD-G-H01 only)
detected.
This function determines whether to use cold junction temperature compensation.
Use this function to measure temperatures at high accuracy when the cold junction
Cold junction temperature
compensation with/without
temperature compensation accuracy ( 1
setting function
The cold junction temperature compensation accuracy can be improved by disabling the
cold junction temperature compensation and providing a precision ice bath externally.
Cold junction temperature
compensation resistor
This function detects a disconnection of connected cold junction temperature compensation
disconnection detection
resistor (RTD).
function
(1)
Warning output function
(2)
This function can convert a measured temperature value into a preset range ratio (%) and
Scaling function
import it into buffer memory.
Offset/gain setting function
This function compensates an error of measured temperature value.
Online module change
A module change is made without the system being stopped.
Table 3.3 Function list
A temperature input value is converted one by one on each channel and a measured
temperature value is output after every conversion. Then the value is stored into buffer
memory.
This processing averages a measured temperature value for each channel and the
averaged value is stored into buffer memory.
Averaging processing contains three methods as described below.
(a) Time average
(b) Count average
(c)
Moving average
Measured temperature values are smoothed by a preset time constant.
Process alarm
When measured temperature value exceeds the preset range, a warning is output.
Rate alarm
When the change of measured temperature value exceeds the preset change, a
warning is output.
Description
Measured temperature value
Measured temperature value
) cannot be taken as a margin of error.
3.2 Function List
1
Refer To
2
Section 3.4.5
3
Section 3.2.1
4
Section 3.4.2
Section 4.5
Section 3.4.15
5
Section 3.2.2
Section 3.4.16
Section 3.2.3
6
Section 4.7
7
Section 3.2.5
Section 3.2.4
8
Section 3.4.17
to
Section 3.4.20
Section 3.4.11
Section 4.6
CHAPTER 7
3
- 5

Advertisement

Table of Contents
loading

This manual is also suitable for:

Sw1d5c-qtiu-eQ68td-g-h01Q68td-g-h02

Table of Contents