4
SETUP AND PROCEDURES BEFORE OPERATION
4.5

Switch Setting for Intelligent Function Module

The settings for the intelligent function module are performed using the I/O assignment
settings for GX Developer.
(1) Setting item
Intelligent function module switch has switches 1 to 5.The setting is executed with 16-
bit data.
When not setting the intelligent function module switch, the default of switches 1 to 5
is 0.
Switch 1
Switch 2
Switch 3
Switch 4
Switch 5
Table 4.4 Intelligent Function Module Switch Settings
Thermocouple type
settings
(CH1 to CH4)
H
CH4 CH3 CH2 CH1
Thermocouple type
settings
(CH5 to CH8)
H
CH8 CH7 CH6 CH5
Offset/gain setting mode
0
0
H
Fixed to 0
H
b7
b6
b5
b4
b3
b2
CH8 CH7 CH6 CH5 CH4 CH3 CH2 CH1
Mode setting, Cold junction compensation setting
0
0
H
Fixed to 0
0
: With cold junction temperature compensation
H
1 to F
*1
: Without cold junction temperature compensation
H
0
: Normal mode
H
1 to F
*1
: offset/gain setting mode
H
* 1 Setting any value within the setting range will provide the same operation.
When the setting range is 1 to F
* 2 Setting a value other than "0" results in an error.
4.5 Switch Setting for Intelligent Function Module
Setting Item
Thermocouple type
Thermocouple K
Thermocouple E
Thermocouple J
Thermocouple T
Thermocouple B
Thermocouple R
Thermocouple S
Thermocouple N
Setting a value other than 0 to 7 results in a range
setting error (error code: 10 ) and the measured
temperature is not converted. (
corresponding channel number.)
b1
b0
0: Factory default setting
1: User range setting
0 : Fixed *2
, set 1 for example.
H
Setting value
0
1
2
3
4
5
6
7
indicates the error
4
- 8
1
2
3
4
5
6
7
8