Siemens SIMATIC ET 200S Operating Instructions Manual page 47

Hide thumbs Also See for SIMATIC ET 200S:
Table of Contents

Advertisement

Notes on the Control Bits
Table 2- 5
Notes on the Control Bits
Control bits
Notes
C_DOPARAM
Change function and behavior of DO1, DO2
The values from bytes 0 to 2 are applied as new function, hysteresis, and pulse duration of DO1,
DO2. This may result in the following error: The conditions for the "Switch at comparison values"
behavior are not fulfilled.
CMP_VAL1
Load comparison value 1
The value from bytes 0 to 3 is transferred to comparison value 1 with the control bit "Load
comparison value CMP_VAL1".
CMP_VAL2
Load comparison value 2
The value from bytes 0 to 3 is transferred to comparison value 2 with the control bit "Load
comparison value CMP_VAL2".
CTRL_DO1
Enable DO1
You use this bit to enable the DO1 output.
CTRL_DO2
Enable DO2
You use this bit to enable the DO2 output.
CTRL_SYN
You use this bit to enable synchronization.
EXTF_ACK
Error acknowledgment
The error bits must be acknowledged with the EXTF_ACK control bit after the cause is removed.
LOAD_PREPARE
Load counter preparatory
The value from bytes 0 to 3 is applied as the load value.
LOAD_VAL
The value from bytes 0 to 3 is loaded directly as the new count value.
RES_STS
Start resetting of status bit
The status bits are reset through the acknowledgment process between the RES_STS bit and the
RES_STS_A bit.
SET_DO1
Control bit DO1
Switches the DO1 digital output on and off when CTRL_DO1 is set.
SET_DO2
Control bit DO2
Switches the DO2 digital output on and off when CTRL_DO2 is set.
SW_GATE
SW gate control bit
The SW gate is opened/closed via the control interface with the SW_GATE bit.
Technological Functions
Operating Instructions, 06/2010, A5E00124867-07
1Count24V
2.6 Count Modes
47