2PULSE
5.7 Application Examples
Programming/Flow Diagram
Below you will find a section from a STEP7 STL program.
The configured start address of the inputs and outputs of the 2PULSE is 256. Configured
with a short control interface.
You use this part of the program to start the process. To do this, memory marker M30.0 must
be set. Set up the off-delay in memory word MW32.
STL
Block:
L
PEB256
T
MB20
L
MW32
T
PAW256
L
10
T
PAB259
L
0
T
MB10
U
M30.0
=
M10.0
L
MB10
T
PAB258
Wiring / Terminal Assignment Diagram
Figure 5-32
340
Description
Read the feedback messages from channel 0 of the 2PULSE
Write off-delay to channel 0 of the 2PULSE
Write on-delay factor 10 x 0.1 to channel 0 of the 2PULSE
Generate SW_ENABLE control signal
Heating process starts
Set SW_ENABLE=1
Write control signals to channel 0 of the 2PULSE
Terminal Assignment of the 2PULSE for Applying a Protective Layer