CJ-series Temperature Control Units
The section provides tables of the events that can occur in the following Units.
CJ1W-TC003
CJ1W-TC004
CJ1W-TC103
CJ1W-TC104
Event code
Event name
04680000 hex
Cold Junction
Sensor Error
34940000 hex
Setting Error
64840000 hex
Sensor Error
64850000 hex
CT Overflow
64860000 hex
Heater Burn-
out Alarm
CJ-series ID Sensor Units
The section provides tables of the events that can occur in the following Units.
CJ1W-V680C11
CJ1W-V680C12
Event code
Event name
046C0000 hex
Unit Status,
Antenna
Power Sup-
ply Error
046D0000 hex
Unit Status,
Memory
Error
046E0000 hex
Results Infor-
mation,
Antenna
Error
046F 0000 hex
Unit Status,
Unit Busy
NJ-series Troubleshooting Manual (W503)
Meaning
Assumed cause
An error occurred in
• Faulty connection to the cold
the cold junction
junction sensor.
sensor.
• The cold junction sensor failed.
There is an illegal
• The set value is incorrect.
setting.
An error occurred in
• Error in input from the Sensor.
the sensor input.
An overflow
• The heater current exceeded
occurred in the CT
55.0 A.
input.
A heater burnout
• The power supply to the heater
occurred.
is not ON.
• The heater is burned out or
deteriorated.
Meaning
Assumed cause
An error occurred in
• An error occurred in the power
the power supply to
supply (24 V) to the Antenna.
the Antenna.
An error occurred
• There is a source of noise
when reading non-
nearby.
volatile memory.
• Non-volatile memory failure
An error occurred in
• The Antenna is not connected.
the Antenna.
• Antenna failure
• The ID Sensor Unit failed.
An error occurred in
• There is a source of noise
an ID Sensor Unit.
nearby.
• The ID Sensor Unit failed.
3 Error Tables
Level
Maj
Prt
Min
Obs
Info
U
S
CJ-series
Temperature
Control Units
Operation
Manual for NJ-
series CPU
Unit (Cat. No.
W491)
U
S
Same as
above.
U
S
Same as
above.
U
S
Same as
above.
U
S
Same as
above.
Level
Maj
Prt
Min
Obs
Info
S
CJ-series ID
Sensor Units
Operation
Manual for NJ-
series CPU
Unit (Cat. No.
Z317)
S
Same as
above.
S
Same as
above.
S
Same as
above.
Reference
3
Reference
3-97

Hide quick links:

Advertisement

Table of Contents
loading

This manual is also suitable for:

Nj501-1500Nj501-1400Nj501-1300Nj301-1200Nj301-1100

Table of Contents