Omron NJ Series Troubleshooting Manual page 134

Machine automation controller sysmac
Hide thumbs Also See for NJ Series:
Table of Contents

Advertisement

3 Error Tables
Event code
Event name
84200000 hex
Link OFF
Error
24200000 hex
Slave Node
Address
Duplicated
34400000 hex
Network
Configura-
tion Informa-
tion Error
50010000 hex
Controller
(Ver. 1.02)
Insufficient
Memory
Warning
84210000 hex
Network
Configura-
tion Error
84220000 hex
Network
Configura-
tion Verifica-
tion Error
84230000 hex
Slave Initial-
ization Error
84280000 hex
Slave Appli-
cation Error
3-72
Meaning
Assumed cause
A Link OFF state
• The Ethernet cable is broken
occurred.
between the master and slaves.
• The Ethernet cable connector is
disconnected.
• The Ethernet cable is not con-
nected.
The same slave
• The same node address is set
address is used for
for more than one slave.
two nodes.
There is an error in
• The power supply to the Con-
the network config-
troller was interrupted or com-
uration information.
munications with the Sysmac
Studio were disconnected while
downloading the network con-
figuration information.
The amount of data
• The amount of data for the
for the EtherCAT
EtherCAT slave configuration,
slave configuration,
network-published information,
network-published
or other data exceeds the value
information, or
that is specified for the CPU
other data exceeds
Unit.
the value that is
specified for the
CPU Unit. You may
not be able to per-
form online editing
or other operations.
The EtherCAT net-
• Slave output ports are con-
work configuration
nected to each other.
is incorrect.
• The master and slave are con-
nected with the slave output
port.
• The number of connected
slaves exceeded the maximum
number of slaves, 192 nodes,
for the EtherCAT master.
A slave that is in the
• A slave that is in the network
network configura-
configuration information is not
tion information is
connected.
not connected. Or,
• There is a node address mis-
a slave that is not in
match.
the network config-
• A different slave from the one
uration information
that is specified in the network
is connected.
configuration information is
connected.
• A slave that is not in the net-
work configuration information
is connected.
• The Ethernet physical layer is
broken between two slaves.
Slave initialization
• An error occurred in EtherCAT
failed.
master processing.
• An initialization error occurred
in the EtherCAT slave.
An error occurred in
• An error was detected in the
the slave applica-
slave's application layer status
tion.
register.
Level
Maj
Prt
Min
Obs Info
S
NJ-series
CPU Unit
Built-in Ether-
CAT Port
User's Manual
(Cat. No.
W505)
S
Same as
above.
S
Same as
above.
S
Same as
above.
S
Same as
above.
S
Same as
above.
S
Same as
above.
S
Same as
above.
NJ-series Troubleshooting Manual (W503)
Reference