Troubleshooting by Remote Controller
4.13 Thermistor Abnormality
C4, C9
Error Code
Applicable
All indoor models
Models
Method of Error
The error is detected by temperature detected by thermistor.
Detection
Error Decision
When the thermistor becomes disconnected or short circuited while the unit is running.
Conditions
Defective connector connection
Supposed
Defective thermistor
Causes
Defective indoor unit PCB
Broken or disconnected wire
Troubleshooting
Caution
Be sure to turn off the power switch before connecting or disconnecting connectors, or parts may be damaged.
Check the connector connection.
Is it connected properly?
Check the thermistor resistance.
Check the contact between thermistor
and PCB.
Is the contact OK?
CHECK 1
Refer to P.152.
103
NO
YES
NO
CHECK 1
Is it normal?
YES
NO
YES
Correct the connection.
Replace the thermistor.
Correct contact.
Replace the outdoor unit PCB.
C4
: Heat exchanger thermistor (R2T)
C9
: Suction air thermistor (R1T)
Service Diagnosis
SiME281501E