Daikin RZQ Series FCQ20EVA Service Manual page 170

Heat pump r410a 60hz
Table of Contents

Advertisement

Troubleshooting by Remote Controller
CHECK 10
Clogged Points
Temperature differences must occur before or after the clogged points!
Check points
1
Around
expansion
mechanism
2
Accumulator
3
Distributor
4
Field piping
5
Stop valve
161
3
4
Indoor Unit
Check factor
Causes
 Dust
Temperature
 Choked moisture
difference
 Reduced effective pipe
 Choked moisture
Frosting
 Dust
Temperature
 Choked moisture
difference
 Reduced effective pipe
 Collapsed pipe
Temperature
difference
 The stop valve is not fully open.
Temperature
difference
1
3
5
2
ACC
COMP
Outdoor Unit
diameter due to adherent
contamination, etc.
diameter due to adherent
contamination, etc.
SiME281501E
Remedies
Replace the electronic
expansion valve.
Blow a nitrogen gas, and
then replace the
refrigerant.
Replace the heat
exchanger or distributor.
Replace the pipe.
Open the stop valve fully.
Service Diagnosis

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents