Field Setting from Remote Controller
Fan Speed Changeover when Heating Thermostat is OFF
By setting to "Set Fan Speed," you can switch the fan speed to the set fan speed when the heating thermostat
is OFF.
 Since there is concern about draft if using "fan speed up when thermostat is OFF," you should take the
setup location into consideration.
Mode No.
12(22)
Fan Speed Changeover when Cooling Thermostat is OFF
By setting to "Set Fan Speed," you can switch the fan speed to the set fan speed when the cooling thermostat
is OFF.
Automatic Restart after Power Failure Reset
For the air conditioners with no setting for the function, the units will be left in the stop condition when the
power supply is reset automatically after power failure reset or the main power supply is turned ON again
after once turned OFF. However, for the air conditioners with the setting (same as factory setting), the units
may start automatically after power failure reset or the main power supply turned ON again (return to the
same operation condition as that of before power failure).
For the above reasons, when the unit is set enabling to utilize "Auto restart function after power failure reset",
utmost care should be paid for the occurrence of the following situation.
Caution 1. The air conditioner starts operation suddenly after power failure reset or
2. In the service work, for example, turning OFF the main power switch during
Mode No.
12(22)
Setting of Normal Airflow
Make the following setting according to the ceiling height. The second code No. is set to "01" at the factory.
 In the Case of FCQ20/24
Mode No.
13 (23)
 In the Case of FCQ36/45
Mode No.
13 (23)
55
First Code No.
3
the main power supply turned ON again. Consequently, the user might be
surprised (with question for the reason why).
the unit is in operation, and turning ON the switch again after the work is
completed start the unit operation (the fan rotates).
First Code No.
6
First code No.
Second code No.
0
First code No.
Second code No.
0
Second Code No.
01
02
Second Code No.
01
02
Setting
Standard • All round
01
outlet
02
High Ceiling (1)
03
Higher Ceiling (2)
Setting
Standard • All round
01
outlet
02
High Ceiling (1)
03
Higher Ceiling (2)
SiME281501E
Setting
LL Fan Speed
Set Fan Speed
Setting
LL Fan Speed
Set Fan Speed
Ceiling height (m)
 2.7
2.7 - 3
3 - 3.5
Ceiling height (m)
 3.2
3.2 - 3.6
3.6 - 4.2
Field Setting