Function Details
4.1.9 Automatic Restart
Purpose
The purpose of the auto-restart function is to automatically resume the same operating mode as when the
unit was operating when the power supply is restored after a power failure.
Do not use the "Automatic Restart" function to daily start/stop the unit.
Precautions when turning OFF power
 When you have to turn OFF the power supply in order to carry out maintenance, make sure to turn the
remote control's ON/OFF switch OFF firstly.
 If you turn OFF the power supply while the remote control's ON/OFF switch is still ON, the "automatic
restart function" automatically starts the indoor unit fan immediately and the outdoor unit fan starts
automatically 3 minutes after the power supply is restarted.
 Do not start/stop the unit by disconnecting the power supply. Stop the unit by stop command from the
remote controller or optional controller before disconnecting the power supply. Be sure that the
compressor and the outdoor unit fans are stopped before disconnecting the power supply so the
"Refrigerant Recovery function" has been finished correctly.
 When restarting the unit after the power supply was disconnected for a longer period leave the unit OFF
with the power supply connected for about half an hour (Refer to "Crankcase Heater Control" &
"Preheating Operation Control").
4.1.10 Fan and Flap Operations
Heating
Operation
Cooling
Operation
31
Hot Start from Defrost
Defrost
Thermostat OFF
Hot Start from
Thermostat OFF (Cold
Air Prevention)
Stop (Error)
Overload Thermostat
OFF
Thermostat ON in
Program Dry Mode
Thermostat OFF in
Program Dry Mode
Cooling Thermostat OFF In Swing Operation
Stop (Error)
Freeze-up Prevention in
Program Dry Mode
(Including Cooling
Operation)
In Swing Operation
In Airflow Direction Setting
In Swing Operation
In Airflow Direction Setting
In Swing Operation
In Airflow Direction Setting
In Swing Operation
In Airflow Direction Setting
In Swing Operation
In Airflow Direction Setting
In Swing Operation
In Airflow Direction Setting
In Swing Operation
In Airflow Direction Setting
In Swing Operation
In Airflow Direction Setting
In Airflow Direction Setting
In Swing Operation
In Airflow Direction Setting
In Swing Operation
In Airflow Direction Setting
Fan
Flap
FCQ
OFF
Horizontal
OFF
Horizontal
Set Position
OFF
Horizontal
OFF
Horizontal
Set Position
LL
Horizontal
LL
Horizontal
Set Position
LL
Horizontal
LL
Horizontal
Set Position
OFF
Horizontal
OFF
Horizontal
LL
Horizontal
LL
Horizontal
Set Position
L
Swing
L
Set Position
Set Position
OFF
Swing
OFF
Set Position
Set Position
Setting
Swing
Setting
Set Position
Set Position
OFF
Horizontal
OFF
Set Position
L
Swing
L
Set Position
Set Position
Function and Control
SiME281501E
Remote
Controller
Indication
Swing
Swing
Swing
Swing
Swing
Swing
Swing
Swing
Swing

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents