2.3.5 80-00 – Inlet water thermistor abnormality
2.3.6 81-00 – Outlet water thermistor abnormality
EBLA09~16DA + EDLA09~16DA
Daikin Altherma 3 M
ESIE20-06A – 2021.03
INFORMATION
If all procedures listed above have been performed and the problem is still present,
contact the helpdesk.
Trigger
Inlet water thermistor
input is out of range.
To solve the error code
INFORMATION
It is recommended to perform the checks in the listed order.
1 Perform a check of the inlet water thermistor. See "3.20 Thermistors" [
Possible cause: Faulty inlet water thermistor.
2 Perform a check of the hydro PCB. See
Possible cause: Faulty hydro PCB.
INFORMATION
If all procedures listed above have been performed and the problem is still present,
contact the helpdesk.
Trigger
Outlet water thermistor
input is out of range.
To solve the error code
INFORMATION
It is recommended to perform the checks in the listed order.
1 Perform a check of the outlet water after backup heater thermistor. See
"3.20 Thermistors" [
Possible cause: Faulty outlet water after backup heater thermistor.
2 Perform a check of the hydro PCB. See
Possible cause: Faulty hydro PCB.
INFORMATION
If all procedures listed above have been performed and the problem is still present,
contact the helpdesk.
Effect
Unit will stop operating.
"3.12 Hydro
Effect
Unit will stop operating.
4
 248].
"3.12 Hydro
2
Troubleshooting
|
Reset
Automatic reset.
4
 248].
4
PCB" [
 160].
Reset
Automatic reset.
4
PCB" [
 160].
Service manual