4.2.5 Starting Control
Starting Control
When compressor start up, the starting frequency is fixed for specified period of time at low frequency to
prevent returning of refrigerant.
Ta: Outdoor air temperature
Compressor
Electronic
expansion valve
Outdoor unit fan
Indoor unit fan
(Thermostat OFF)
(Remote controller OFF)
A Hz
Function and Control
Pressure
Pressure
equalizing
equalizing
complete
start
Pressure equalizing
control before
compressor start
Starting control
Cooling or
Heating ( < 25˚C)
65 pls
Heating ( > 25˚C)
480 pls
8 Step ON
(Cooling Ta ≤ 40˚C, Heating Ta > 26˚C)
OFF
(Cooling Ta > 40˚C, Heating Ta < 26˚C)
Set fan speed (Cooling)
LL (Heating)
OFF
10~120 sec.
RZQ20/24LVA
118.5 Hz
Starting
control
complete
A Hz
L (Cooling)
M
L
(Heating)
Function Details
RZQ36/45LVA,
RZQ45/48MYL
112 Hz