SiME281501E
4.9
Abnormal Power Supply Voltage
A8
Error Code
Applicable
FBQ
Models
Method of Error
Detect error checking the input voltage of fan motor
Detection
Error Decision
When the input voltage of fan motor is 150V and less, or 386V and more
Conditions
Power supply voltage error
Supposed
Defective connection on signal line
Causes
Defective wiring
Instantaneous blackout, others
Troubleshooting
Caution
Be sure to turn off the power switch before connecting or disconnecting connectors, or parts may be damaged.
Check the condition of the power
supply.
Check if power supply voltage is
220V - 240V ± 10%.
Check if there is power open phase
or defective wiring.
Check if power supply voltage side
unbalance is within 6V.
problems on the condition of
power supply described
Service Diagnosis
There are
YES
above.
NO
Error is
YES
displayed again.
NO
Troubleshooting by Remote Controller
Correct any fault.
Check and correct each wiring.
It is possible to have external
factor, such as brownout and
instantaneous blackout.
98