Service Mode

3. Service Mode

3.1

BRC1C61/BRC1D61

3.1.1 Display Service Data
1. Enter the field setting mode.
Press the INSPECTION/TEST button for 4 seconds or more.
2. Enter the service mode.
After having entered the field setting mode, press the INSPECTION/TEST button for 4 seconds or more.
3. Select the mode No.
Set the desired mode No. with the up/down temperature setting button.
4. Select the unit No.
Select the indoor unit No. set with the time mode START/STOP button.
5. Select the desired error history No. or thermistor data No. with "
6. Each data displays (Refer to the table below display)
7. Return to the normal operation mode.
Press the INSPECTION/TEST button once.
Mode No.
Function
40
Error History
41
Thermistor Data
Display
17
Unit No.
Second
Code No.
3
First
Code No.
2 7
1
Content and Operation Method
You can change the history with the
programming time up-down button.
Select the display thermistor with
the programming time up-down
button
Display thermistor
00: Room temperature thermistor in
remote controller
01: Suction air thermistor
02: Heat exchanger thermistor
4
5
3
6
" or "
Example of Remote Controller Display
UNIT No.
SiME281501E
Mode No.
Field
Setting
Mode
" button.
past error
code
UNIT
N
O.
CODE
SETTING
Error history
: Newest
1
: Oldest
3
∗ "00" displayed for 4 and subsequent.
Thermistor type
Temperature
SETTING
Remote Controller