2.3.1 Detailed Explanation of Setting Modes
Filter Sign Setting
If switching the filter sign ON time, set as given in the table below.
First Code
Mode No.
10 (20)
Filter Type
When a ultra long life filter is installed, the filter sign timer setting must be changed.
Mode No.
10 (20)
Selection of Thermistor
Select the thermistor to control room temperature.
Mode No.
10 (20)
The factory setting for the Second Code No. is "01" and room temperature is controlled by the indoor unit
suction air thermistor.
When the Second Code No. is set to "02", room temperature is controlled by the suction air thermistor and
remote controller thermistor.
"Filter Cleaning" Displayed or Not Displayed
Whether or not to display "Filter Cleaning" after operation of certain duration can be selected.
Mode No.
10 (20)
Fan Speed OFF when Thermostat is OFF
When the cool/heat thermostat is OFF, you can stop the indoor unit fan by switching the setting to "Fan OFF."
 Used as a countermeasure against odor for barber shops and restaurants.
Mode No.
11(21)
Airflow Adjustment (AUTO)
External Static Pressure Settings
Make settings in either method (a) or method (b) as explained below.
(a) Use the airflow auto adjustment function to make settings.
Airflow auto adjustment: The volume of blow-off air is automatically adjusted to the rated quantity.
(b) Select External Static Pressure with Remote Controller Check that 01 (OFF) is set for the "Second Code
No." in "Mode No. 21" for airflow adjustment on an indoor unit basis in Table below. The "Second Code
No." is set to 01 (OFF) at factory setting. Change the "Second Code No." as shown in Table according to
the external static pressure of the duct to be connected.
Mode No.
11 (21)
Field Setting
Second
Standard Filter
No.
Code No.
01
0
02
First Code No.
1
First Code No.
2
First Code No.
3
First Code No.
2
First Code No.
7
Long Life Filter
200 hrs.
2,500 hrs.
100 hrs.
1,250 hrs.
Second Code No.
01
02
Second Code No.
Thermistor that controls room temperature
Room temperature thermistor in the remote
01
controller and suction air thermistor for indoor
unit
02
Indoor unit suction air thermistor
Second Code No.
01
02
Second Code No.
01
02
Second Code No.
01
02
Completion of airflow adjustment
03
Start of airflow adjustment
Field Setting from Remote Controller
Ultra Long Life
Filter
Contamination
10,000 hrs.
Light
Contamination
5,000 hrs.
Heavy
Setting
Long Life Filter
Ultra Long Life Filter
"Filter Cleaning" display
Display
No display
Setting
Fan OFF
Airflow adjustment
OFF
Setting
54