4.27 Outdoor Unit PCB Abnormality
L1
Error Code
Applicable
RZQ
Models
Detect error by current value during waveform output before compressor startup.
Method of Error
Detect error by current sensor value during synchronized operation at the time of startup.
Detection
Detect error using an SP-PAM series capacitor overvoltage sensor.
When overcurrent is detected at the time of waveform output before operating the
Error Decision
Conditions
When the current sensor error during synchronized operation
When overvoltage occurs in SP-PAM
In case of IGBT error
Defective outdoor unit PCB (A1P)
Supposed
Causes
Defective connection of compressor connector
Defective outdoor unit fan motor
Broken fuse
External factor (Noise, etc.)
Service Diagnosis
compressor
IPM failure
Current sensor failure
SP-PAM failure
Defective of IGBT or drive circuit
Troubleshooting by Remote Controller