Instructions That Need To Be Executed Again In A New Control System - Mitsubishi Electric MELSEC iQ-R-R00CPU User Manual

Melsec iq-r series cpu module application user's manual
Table of Contents

Advertisement

Instructions that need to be executed again in a new control
system
For an instruction that requires several scans for completing the processing, the instruction will be continuously executed
when the system switching is performed during execution of the instruction. When a completion device has been used in an
execution program of the control system, the completion device will not turn on even though the instruction is completed after
the system switching from the control system to the standby system. However, the completion device will turn on after the
system switching from the control system to the standby system and then to the control system again. Note that the
completion state of the completion device is not reflected to the tracking device. When the system switching is performed
during execution of an instruction, execute the instruction again as required.
Classification
Data processing instructions
Reading/writing data instructions
Open/close processing instructions
Socket communications instructions
SLMP frame send instruction
File transfer function instruction
Module dedicated instructions
For some instructions, an error will occur if an instruction is executed during execution of the same instruction. For the
operation for each instruction that is executed again during execution of the same instruction, refer to the following.
 MELSEC iQ-R Programming Manual (CPU Module Instructions, Standard Functions/Function Blocks)
 MELSEC iQ-R Programming Manual (Module Dedicated Instructions)
Instruction symbol
SORTD(_U), DSORTD(_U)
SP.DEVST, SP.FREAD, SP.FWRITE
SP.SOCOPEN, SP.SOCCLOSE
SP.SOCRCV, S.SOCRCVS, SP.SOCSND, SP.SOCCINF, SP.SOCCSET,
SP.SOCRMODE, S(P).SOCRDATA
SP.SLMPSND
SP.FTPPUT, SP.FTPGET
Instructions that require several scans for completing processing
29 PRECAUTIONS ON PROGRAMMING
29.1 Instructions Not Available in Redundant System
29
503