Online module change function

The following is the list of special register areas relating to the online module change function.
No.
Name
SD1600
Module selection
(base unit No.)
SD1601
Module selection (slot
No.)
SD1602
I/O No. of the module
being changed online
SD1617
Online module
change progress
status
SD1618
Online module
change error code
SD1619
Disable request error
code during online
module change
APPX
874
Appendix 5 List of Special Register Areas
Data stored
Details
Base unit No. where
The base unit number where the online change target module is
the online change
mounted is specified.
target module is
0: Main base unit
mounted
1: Extension base unit 1
7: Extension base unit 7
FFFFH: Not specified (Default)
The stored value returns to its default (FFFFH) upon completion of
the online module change processing. When changing a module
directly, the system stores the corresponding base unit number
upon removal of the target module.
Slot No. where the
The slot number where the online change target module is
online change target
mounted is specified.
module is mounted
0: Slot No.0
1: Slot No.1
11: Slot No.11
FFFFH: Not specified (Default)
The specified value returns to its default (FFFFH) upon completion
of the online module change processing. When changing a module
directly, the system stores the corresponding slot number upon
removal of the target module.
I/O No. of the module
The value of the I/O number of the module being changed online
being changed online
divided by 16 is stored.
Other than FFFFH: I/O No.  16
FFFFH: Not specified (Default)
The stored value returns to its default (FFFFH) upon completion of
the online module change processing.
Online module
The online module change progress status is stored.
change progress
0: Normal operation
status
1: Module being selected
2: Module selected
3: Module removal requested
4: Module removal ready
5: Module removed
6: Module mounted
7: Module being recognized
8: Module recognized
9: Module control resumed
The value becomes 0 upon completion of the online module
change processing.
0: Normal operation
The corresponding error code is stored when an error is detected
Other than 0: Error
during online module change. For the value stored, refer to the list
code
of error codes. ( Page 786 Error codes related to the online
module change function) This register is cleared to 0 when the
error cause is eliminated and the online module change related
request is executed. However, the error code needs to be cleared
to 0 before module selection since this register is not cleared to 0 if
an error occurs in selecting a module.
0: Normal operation
The corresponding error code is stored when a disable request is
Other than 0: Error
executed during online module change. The error code is cleared
code
to 0 when the error cause is eliminated and the online module
change related request is executed.
For the value stored, refer to the list of error codes. ( Page 786
Error codes related to the online module change function)
Set by
CPU
(setting
timing)
S (Status
RnP
change)/U
RnPSF
(Request)
S (Status
RnP
change)/U
RnPSF
(Request)
S (Status
RnP
change)
RnPSF
S (Status
RnP
change)
RnPSF
S (Status
RnP
change)/U
RnPSF
(Request)
S (Status
RnP
change)
RnPSF

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents