Occurrence of a cause of the system switching failure
The BACKUP LED flashes when a cause of the system switching failure has been generated.
The cause of the BACKUP LED flashing can be checked in SD1642 (BACKUP/SEPARATE LED flashing
cause). Check SD1642 and eliminate the cause to flash the LED.

Check method of system switching information

The following table lists the check methods of system switching information at system switching (automatic system switching
and manual system switching).
Check method
Event history
Special relay (SM)/Special register (SD)
CTRL LED and SBY LED of the redundant
function module
When the systems have been switched, check the switching cause or detailed information and take corrective action to
restore the system to a normal state as required.
Event history
The information related to system switching results, system switching cause, and control system/standby system transitions
can be checked with the event history of the engineering tool.
When the systems are switched, the following items are stored in the event history of both systems.
• Automatic system switching: "System switching (system)" (event code: 00F00)
• Manual system switching: "System switching (user)" (event code: 2B000)
When the systems are switched by the SP.CONTSW instruction, the system switching instruction ID number specified with
the SP.CONTSW instruction is also stored.
Special relay/Special register
System switching results and detailed information can be checked with the special relay and special register.
• Whether the systems have been switched or not can be checked by checking SD1649 (System switching cause (when the
systems are successfully switched)). When the systems have been switched, the system switching cause is stored in
SD1649 of the control system and standby system.
• If the systems have not been switched even after a system switching cause is generated, the cause why the systems have
not been switched can be checked by checking SD1644 (Cause of system switching failure). The switching cause is stored
in SD1643 (System switching cause).
For the values stored in the special relay and special register, refer to the following.
• Special relay ( Page 829 Redundant function)
• Special register ( Page 875 Redundant function)
Information
System switching result, system switching cause, and control system/
standby system transition
System switching result and detailed information
System switching result
Reference
Page 617 Event history
Page 617 Special relay/Special
register
Page 618 CTRL LED and SBY
LED of the redundant function
module
37 FUNCTIONS
617
37.1 System Switching