Fixed scan function information

The following is the list of special relay areas relating to the fixed scan function information.
No.
Name
SM480
Cycle error flag for inter-
module synchronous
interrupt program (I44)
SM481
Cycle error flag for multiple
CPU synchronization
interrupt program (I45)
SM484
Execution section excess
error flag for multiple CPU
synchronization interrupt
program
SM488
Inter-module
synchronization error (out of
synchronization was
detected on the CPU
module)
*1 There are restrictions on the firmware version of the supported CPU module and software version of the engineering tool. ( Page
1008 Added and Enhanced Functions)
Data stored
Details
Off: No error for the inter-
• This relay switches to on when the inter-
module
module synchronous interrupt program
synchronization
(I44) has not been completed within the
program (Normal)
specified inter-module synchronization
On: Error state for the
cycle or the program cannot be executed
inter-module
due to various reasons, such as
synchronization
execution of a higher-priority interrupt
program
program and interrupt disabling by the
instruction execution.
• The ON state is maintained even after the
program is later completed within the
specified inter-module synchronization
cycle (Clear by turning power off and on
or resetting).
Off: No error for the
• This relay switches to on when the
multiple CPU
multiple CPU synchronization program
synchronization
(I45) has not been completed within the
program (Normal)
specified fixed scan communication cycle
On: Error state for the
or the program cannot be executed due to
multiple CPU
various reasons, such as execution of a
synchronization
higher-priority interrupt program and
program
interrupt disabling by the instruction
execution.
• The ON state is maintained even after the
program is later completed within the
specified fixed scan communication cycle
(Clear by turning power off and on or
resetting).
Off: No execution section
• This relay switches to on when the
excess error for the
program is executed exceeding the
multiple CPU
program execution section within the
synchronization
specified multiple CPU synchronization
interrupt program
cycle.
(Normal)
• The ON state is maintained even after the
On: Execution section
program is later completed within the
excess error state for
multiple CPU synchronous interrupt
the multiple CPU
program execution section (cleared by
synchronization
turning power off and on or resetting).
interrupt program
Off: No error (Normal)
• This relay switches to on when the inter-
On: Error
module synchronization signal cannot be
identified within the inter-module
synchronization cycle specified in the
parameter or more than one signal has
been identified within the same inter-
module synchronization cycle.
• The ON state is maintained even after the
inter-module synchronization signal can
be later identified within the specified
inter-module synchronization cycle
(cleared by turning power off and on or
resetting).
Set by (setting timing) CPU
S (Status change)
S (Status change)
S (Status change)
S (Status change)
Appendix 4 List of Special Relay Areas