Link Special Relay (Sb) - Mitsubishi Electric MELSEC iQ-R-R00CPU User Manual

Melsec iq-r series cpu module application user's manual
Table of Contents

Advertisement

If more than 16 annunciators are turned on, the 17th annunciator onwards are not stored into SD64 to SD79.
However, if the numbers of annunciators registered in SD64 to SD79 are turned off, the lowest numbers,
which are not registered in SD62 to SD79, of the numbers of annunciators which were turned on for the 17th
on and after, are stored into SD64 to SD79.
SD62
SD63
SD64
SD65
SD79
(1)
(1) Annunciators have been stored for the maximum number (16).
(2) Because annunciators have been stored for the maximum number, the value does not change.
(3) The smallest number is stored.
(4) Turn on the 17th device.
(5) Turn on the 18th device.
(6) Turn off the first device.

Link special relay (SB)

The communication status and error detection status of network modules, such as the CC-Link IE Controller Network module,
are output to the link special relay (J\SB) on the network. The link special relay (SB) is a device for using as a refreshing
target of link special relays in the network. The part which is not used for refreshing can be used for other applications.
(1)
SB65
Program
(1) The network status is checked.
21 DEVICES
336
21.3 User Device
(4)
(5)
SET F100
SET F50
10
10
SD62
SD62
16
SD63
16
SD63
10
SD64
10
SD64
11
11
SD65
SD65
SD79
SD79
25
25
(2)
CPU module
Used in a program.
SB0065
(6)
RST F10
10
SD62
11
16
SD63
16
10
SD64
11
11
SD65
12
(3)
SD79
25
50
IE Controller Network module
SB
Refresh
CC-Link
SB
Set the own
SB0065
station link status.

Hide quick links: